Property |
Unit |
Requirement |
Result |
---|---|---|---|
Board conforms to CAN/ULC-S701-05 and CAN/ULC-S701-11 |
— |
Pass |
Pass: Type 1 |
Water vapour permeance conforms to ASTM E 96/E 96M-05, (Desiccant Method) |
ng/Pa∙s∙m2 |
≤ 60 |
4.23 |
Water vapour permeance after weathering and heat aging |
ng/Pa∙s∙m2 |
≤ 60 |
5.08 |
Property |
Unit |
Requirement |
Result |
---|---|---|---|
Foil conforms to CAN/CGSB-51.33-M89 |
— |
Pass |
Pass: Type 2 |
Emissivity |
— |
Report value |
0.036 |
Emissivity after weathering and heat aging |
% |
Max. 5% higher than original value |
−2.7 Footnote (1) |
Water vapour permeance |
ng/Pa∙s∙m2 |
≤ 60 |
2.1 |
Water vapour permeance after weathering and heat aging |
ng/Pa∙s∙m2 |
≤ 60 |
14.4 |
Adhesion strength (peel force) |
N |
Report value |
2.9 |
Adhesion strength after weathering and heat aging |
% |
≥ 85% of original value |
89.7 |
Property |
Unit |
Requirement |
Result |
|
---|---|---|---|---|
k1 Footnote (1) |
k2 Footnote (1) |
|||
Room-side air temperature |
°C |
Report value |
20 |
20 |
Weather-side air temperature |
°C |
Report value |
−35 |
−35 |
Thermal resistance of the wall Footnote (2) |
m2∙K/W |
Report value |
3.10 |
3.03 |
Design thermal resistance of the wall Footnote (3) |
m2∙K/W |
Report value |
3.25 |
3.18 |
Contribution of the furred air space assembly to the thermal resistance of the wall Footnote (4), Footnote (5) |
m2∙K/W |
Report value |
0.62 |
0.55 |
Property |
Unit |
Requirement |
Result |
|
---|---|---|---|---|
k1 Footnote (1) |
k2 Footnote (1) |
|||
Room-side air temperature |
°C |
Report value |
20 |
20 |
Weather-side air temperature |
°C |
Report value |
−35 |
−35 |
Thermal resistance of the wall Footnote (2) |
m2∙K/W |
Report value |
3.02 |
2.95 |
Design thermal resistance of the wall Footnote (3) |
m2∙K/W |
Report value |
3.17 |
3.10 |
Contribution of the furred air space assembly to the thermal resistance of the wall Footnote (4), Footnote (5) |
m2∙K/W |
Report value |
0.54 |
0.47 |
Property |
Unit |
Requirement |
Result |
|
---|---|---|---|---|
k1 Footnote (1) |
k2 Footnote (1) |
|||
Room-side air temperature |
°C |
Report value |
20 |
20 |
Weather-side air temperature |
°C |
Report value |
−35 |
−35 |
Thermal resistance of the wall Footnote (2) |
m2∙K/W |
Report value |
2.96 |
2.89 |
Design thermal resistance of the wall Footnote (3) |
m2∙K/W |
Report value |
3.11 |
3.04 |
Contribution of the furred air space assembly to the thermal resistance of the wall Footnote (4), Footnote (5) |
m2∙K/W |
Report value |
0.48 |
0.41 |
Property |
Unit |
Requirement |
Result |
|
---|---|---|---|---|
k1 Footnote (1) |
k2 Footnote (1) |
|||
Room-side air temperature |
°C |
Report value |
20 |
20 |
Weather-side air temperature |
°C |
Report value |
−35 |
−35 |
Thermal resistance of the wall Footnote (2) |
m2∙K/W |
Report value |
3.16 |
3.09 |
Design thermal resistance of the wall Footnote (3) |
m2∙K/W |
Report value |
3.31 |
3.24 |
Contribution of the furred air space assembly to the thermal resistance of the wall Footnote (4), Footnote (5) |
m2∙K/W |
Report value |
0.68 |
0.61 |
Property |
Unit |
Requirement |
Result |
|
---|---|---|---|---|
k1 Footnote (1) |
k2 Footnote (1) |
|||
Room-side air temperature |
°C |
Report value |
20 |
20 |
Weather-side air temperature |
°C |
Report value |
−35 |
−35 |
Thermal resistance of the wall Footnote (2) |
m2∙K/W |
Report value |
3.15 |
3.08 |
Design thermal resistance of the wall Footnote (3) |
m2∙K/W |
Report value |
3.30 |
3.23 |
Contribution of the furred air space assembly to the thermal resistance of the wall Footnote (4), Footnote (5) |
m2∙K/W |
Report value |
0.67 |
0.60 |