Results of Testing the Material Requirements of the Products

Property

Requirement

Result

Pipe and fittings (for use in potable water and hydronic heating and cooling systems)

Meet requirements of CAN/CSA-B137.11

Pass

Glass fibre pipe insulation

Meet requirements of ASTM C 547, “Standard Specification for Mineral Fiber Pipe Insulation.” Insulation products must be tested and approved by a certification agency recognized by CCMC. Consult with Aquatherm for a list of acceptable pipe insulations.

Pass

Results of Testing the Performance Properties of the Products

Property

Requirement

Result

Flame-spread rating

≤ 25

Pass

Smoke-developed classification

≤ 50

Pass

Fire-stop system rating Footnote (1)

Certified to CAN/ULC-S115

F-rating