Results of Testing of the Performance Requirements for the Product

Test

Unit

Requirement

Result

Tested as per CAN/ULC-S741 with five 1-m2 membrane specimens and measured for air permeance at a minimum of six air pressure differentials (ΔP) between 0 and 300 Pa

unconditioned (prior to UV and heat aging)

L/(s·m2)

Air leakage rate at 75 Pa ΔP (based on linear regression of 30 data points) ≤ 0.02 L/(s·m2)

0.0014

conditioned (after UV and heat aging)

L/(s·m2)

Where less than 0.01 L/(s·m2) for unconditioned specimens, the increase of the air leakage rate at 75 Pa ΔP for conditioned specimens ≤ 0.001 L/(s·m2).

0.0016Footnote (1)

0.0002Footnote (2)

Water vapour permeance

infiltration direction

ng/(Pa·s·m2)

Where less than 60 ng/(Pa·s·m2), the location of the product installation is restricted by the requirements listed in Article 9.25.1.1. of Division B of the NBC 2015.

677.5

exfiltration direction

ng/(Pa·s·m2)

689.9