Results of testing the product to the CCMC Technical Guide for Air Barrier Materials

Test

Requirement

Result

Five 1 m2 membrane specimens tested and measured for air permeance at a minimum of six air pressure differentials (DP) between 0 and 250 Pa (unconditioned specimens)

Air leakage rate at 75 Pa ΔP (based on linear regression of 30 data points) ≤ 0.02 L/(s·m2)

0.004 L/(s·m2)

Five 1 m2 membrane specimens tested and measured for air permeance at a minimum of six air pressure differentials (ΔP) between 0 and 250 Pa (conditioned specimens)

Where less than 0.01 L/(s·m2) for unconditioned specimens, the air leakage rate for conditioned specimens must not increase by more than 0.001 L/(s·m2) at 75 Pa pressure difference.

Pass

Water vapour transmission

Report value

180 ng/(Pa∙s∙m2)