Content page
From [Institution name]
Wood-Frame Walls |
Requirement |
Result |
|
---|---|---|---|
Original "CABS" (25-mm "FOAMULAR® CodeBord®" XPS with foam gaskets beneath XPS panel joints) |
Specimen no. 1 – opaque wall |
Air leakage rateFootnote (1) at 75 Pa ΔP ≤ 0.05 L/(s·m2) |
0.048 L/(s·m2)Footnote (3) |
Specimen no. 2 – continuity at penetrations |
|||
Specimen no. 3 – continuity at foundation and brick straps |
|||
Hybrid "CABS" (20-mm "FOAMULAR® CodeBord®" XPS(R4) with exterior taped seams) |
Specimen no. 1 – opaque wall |
Air leakage rateFootnote (2) at 75 Pa ΔP ≤ 0.05 L/(s·m2) |
0.042 L/(s·m2)Footnote (3) |
Specimen no. 2 – continuity at penetrations, foundation, brick straps |
|||
Hybrid "CABS" (25-mm "FOAMULAR® CodeBord®" XPS(R5) with exterior taped seams) |
Specimen no. 1 – opaque wall |
Air leakage rateFootnote (1) at 75 Pa ΔP ≤ 0.05 L/(s·m2) |
0.040 L/(s·m2)Footnote (3) |
Specimen no. 2 – continuity at penetrations, foundation, brick straps |
Drying Potential Based on Water Vapour Permeance (WVP) of Outermost Layer of Wall Assembly (ng/Pa·s·m2) |
Maximum Permissible Air Leakage Rates (L/s·m2) @ 75 Pa |
---|---|
15 < WVPFootnote (1) ≤ 60 |
0.05Footnote (1) |
60 < WVP ≤ 170 |
0.10 |
170 < WVP ≤ 800 |
0.15 |
> 800 |
0.20 |
Component |
Requirement |
Result |
|
---|---|---|---|
Original "CABS" |
"FOAMULAR® CodeBord®" |
Air permeance before and after aging (ASTM D 726-84) < 10% increase |
PassedFootnote (1) |
Thermal resistance after heat aging and weathering 90% retention |
Passed |
||
"FoamSealR™" polyethylene sealing gasket |
Oxidative induction time (OIT) ≥ 30 minutes |
Passed |
|
proprietary spray-in-place foam sealant |
Air leakage after aging ≤ 0.5 L/s at 75 Pa ΔP |
Passed |
|
caulking sealant for protection from weather |
Meets ASTM C 920-14 |
Not evaluated for durability of air leakage performance |
|
Hybrid "CABS" |
"FOAMULAR® CodeBord®" |
Air permeance before and after aging as per ULC S741 aging (i.e., 28 cycles of UV exposure + heat aging 772 h at 50°C) < 10% increase |
Passed |
"JointSealR® Foam Joint Tape" |
See CCMC 14003-R |
Passed |
|
"FlashSealR® Foam Flashing Tape" |
See CCMC 14003-R |
Passed |
XPS Panel |
Attachment Schedule |
Wind Load Limit (Q 50) |
Deflection Beyond Framing (Max.) |
---|---|---|---|
20-mm "FOAMULAR® CodeBord®" |
Nails with 25-mm (1-in.) diameter cap washers, at 150 mm (6 in.) o.c., into wood studs at 400 mm (16 in.) o.c. |
Q50 ≤ 0.75 kPa |
22 mm |
25-mm "FOAMULAR® CodeBord®" |
Nails with 25-mm (1-in.) diameter cap washers, at 150 mm (6 in.) o.c., into wood studs 600 mm (24 in.) o.c. |
Q50 ≤ 0.55 kPa |
11 mm |