Results of Testing of Air Leakage Rate of the Product After Wind Loading

Wood-Frame Walls

Requirement

Result

Original "CABS" (25-mm "FOAMULAR® CodeBord®" XPS with foam gaskets beneath XPS panel joints)

Specimen no. 1 – opaque wall

Air leakage rateFootnote (1)   at 75 Pa ΔP ≤ 0.05 L/(s·m2)

0.048 L/(s·m2)Footnote (3)

Specimen no. 2 – continuity at penetrations

Specimen no. 3 – continuity at foundation and brick straps

Hybrid "CABS" (20-mm "FOAMULAR® CodeBord®" XPS(R4) with exterior taped seams)

Specimen no. 1 – opaque wall

Air leakage rateFootnote (2) at 75 Pa ΔP ≤ 0.05 L/(s·m2)

0.042 L/(s·m2)Footnote (3)

Specimen no. 2 – continuity at penetrations, foundation, brick straps

Hybrid "CABS" (25-mm "FOAMULAR® CodeBord®" XPS(R5) with exterior taped seams)

Specimen no. 1 – opaque wall

Air leakage rateFootnote (1)   at 75 Pa ΔP ≤ 0.05 L/(s·m2)

0.040 L/(s·m2)Footnote (3)

Specimen no. 2 – continuity at penetrations, foundation, brick straps

Permissible Air Leakage Rates

Drying Potential Based on Water Vapour Permeance (WVP) of Outermost Layer of Wall Assembly (ng/Pa·s·m2)

Maximum Permissible Air Leakage Rates (L/s·m2) @ 75 Pa

15 < WVPFootnote (1)   ≤ 60

0.05Footnote (1)

60 < WVP ≤ 170

0.10

170 < WVP ≤ 800

0.15

> 800

0.20

Results of Testing of Durability of Components of the Product

Component

Requirement

Result

Original "CABS"

"FOAMULAR® CodeBord®"

Air permeance before and after aging (ASTM D 726-84) < 10% increase

PassedFootnote (1)

Thermal resistance after heat aging and weathering 90% retention

Passed

"FoamSealR™" polyethylene sealing gasket

Oxidative induction time (OIT) ≥ 30 minutes

Passed

proprietary spray-in-place foam sealant

Air leakage after aging ≤ 0.5 L/s at 75 Pa ΔP

Passed

caulking sealant for protection from weather

Meets ASTM C 920-14

Not evaluated for durability of air leakage performance

Hybrid "CABS"

"FOAMULAR® CodeBord®"

Air permeance before and after aging as per ULC S741 aging (i.e., 28 cycles of UV exposure + heat aging 772 h at 50°C) < 10% increase

Passed

"JointSealR® Foam Joint Tape"

See CCMC 14003-R

Passed

"FlashSealR® Foam Flashing Tape"

See CCMC 14003-R

Passed

Wind Load Resistance for the Product

XPS Panel

Attachment Schedule

Wind Load Limit (Q 50)

Deflection Beyond Framing (Max.)

20-mm "FOAMULAR® CodeBord®"

Nails with 25-mm (1-in.) diameter cap washers, at 150 mm (6 in.) o.c., into wood studs at 400 mm (16 in.) o.c.

Q50  ≤ 0.75 kPa

22 mm

25-mm "FOAMULAR® CodeBord®"

Nails with 25-mm (1-in.) diameter cap washers, at 150 mm (6 in.) o.c., into wood studs 600 mm (24 in.) o.c.

Q50  ≤ 0.55 kPa

11 mm